DCP-SOM-A / -AI - CLASS A SUPERVISED OUTPUT MODULE
HOCHIKI
STANDARD FEATURES
• Built-in SCI circuitry (SOM-AI only)
• Flexible application
• Quick response to emergency conditions
• Operation parameters are maintained by the
module, and individual communication with the
control system during emergency conditions
is not required
• Contacts are rated 2.0 Amps @ 24VDC
• Programming is highly flexible providing 16
priority states plus zoning capability
• Programmed device output is turned off, silenced,
or programmed to output the selected pattern
• UL 864 Listed
DESCRIPTION
The Class A Supervised Output Modules (DCP-SOM-A &
SOM-AI) have been designed to provide application
flexibility and quick response to emergency conditions.
Flexibility is provided by a wide range of operating
modes, including supporting multi-zone operations, and/
or functions, up to 16 different modulation patterns and
multi-state programming. The operating parameters for
the DCP-SOM-A & -AI are maintained by the module
and do not require individual communication with the
control system during emergency conditions to operate.
The control panel simply broadcasts system conditions
on the Signaling Line Circuit (SLC) and the DCP-SOM-A
& -AI modules do the rest based upon the custom
configuration. Each DCP-SOM-A & -AI provides a single
Class B or Class A circuit rated for 2.0 Amps @ 24
VDC. Each DCP-SOM-A & -AI also requires a 24 VDC
power source in addition to the SLC.
SPECIFICATIONS
Supply Voltage (S-SC) 25.3 ~ 39 VDC
Auxiliary Supply Voltage 24 VDC
Average Current Consumption
SOM-AI - 420μA (Typical), SOM-A - 220μA (Typical)
(on S-SC Line) Maximum 6mA: Red Alarm LED On
Current Consumption on
Auxiliary Power Lines Typical 50μA
SCI On Resistance
40m ohm Max. (Normal Condition)
SCI Fault Detection Threshold 12 volts (Typical)